Thermal motor monitoring – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 94

Advertising
background image

Safety instructions

Thermal motor monitoring

2

l

94

EDK82EV222 DE/EN/FR 13.0

Thermal motor monitoring

Description
With the I

2

t monitoring you can monitor self−ventilated three−phase AC motors thermally without

sensors.

)

Note!

ƒ

The I

2

xt monitoring is based on a mathematical model which calculates a thermal

motor utilisation from the motor currents measured.

ƒ

However, the I

2

xt monitoring is no full motor protection, since other influences on

the motor utilisation cannot be detected, like changed cooling conditions (e.g.
cooling air flow interrupted or too warm).

ƒ

You can only obtain full motor protection if the motor is equipped with a PTC
thermistor or a thermal contact.

J

Warnings!

If you use the I

2

xt function in UL−approved systems for thermal motor monitoring:

ƒ

The I

2

xt function is UL−approved.

ƒ

In UL−approved systems no additional protective measures for the motor are
required.

For devices from software version V3.9 (nameplate data: E82xV... xx 39), an additional
setting is required!

ƒ

Activate the starting value 50% for the I

2

xt function:

Add 128 to the value displayed in Code C0311.

ƒ

Example:

C0311 = 1 (Lenze setting)

Setting for UL−approved systems: C0311 = 129