Electrical installation – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 122

Advertising
background image

Electrical installation

Mains connection
Fuses and cable cross−sections according to EN 60204−1

5

l

122

EDK82EV222 DE/EN/FR 13.0

Fuses and cable cross−sections according to EN 60204−1

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a fault
current monitoring unit (RCM) is used for protection in the case of direct or indirect contact, only
one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a

1−phase system

Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system by
using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply and controller.

Observe all national and regional regulations!

Operation with increased rated power

,

System Manual

Operation at rated power

8200 vector

Rated fuse current

Cable cross−section

ELCB

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, N, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Mains 1/N/PE AC 230/240 V − operation without mains choke/mains filter

E82xV251K2C

10

C10

1.5

³ 30

E82xV371K2C

10

C10

1.5

E82xV551K2C

10

B10

1.5

E82xV751K2C

16

B16

2.5

4

)

E82xV152K2C

20

B20

2 x 1.5

E82xV222K2C

Operation only permitted with mains choke or mains filter

Mains 1/N/PE AC 230/240 V − operation with mains choke/mains filter