Fault messages, Troubleshooting and fault elimination – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 158

Advertising
background image

Troubleshooting and fault elimination

Fault elimination
Fault messages

8

l

158

EDK82EV222 DE/EN/FR 13.0

Fault messages

Keypad

PC

1)

Fault

Cause

Remedy

noer

0

No fault

ccr

a

71

System fault

Strong interference injections on
the control cables

Shield control cables

Earth loops in the wiring

ce0

a

61

Communication
error on AIF
(configurable in
C0126)

Faulty transmission of control
commands via AIF

Insert the communication module
firmly into the diagnosis terminal

ce1

a

62

Communication
error on CAN−IN1
with sync control

CAN−IN1 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/1, if necessary

ce2

a

63

Communication
error on CAN−IN2

CAN−IN2 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/2, if necessary

ce3

a

64

Communication
error on CAN−IN1
with event or time
control

CAN−IN1 object receives faulty
data, or communication is
interrupted

l

Check plug connection bus
module

ó FIF

l

Check transmitter

l

Increase monitoring time in
C0357/3, if necessary

ce4

a

65

BUS−OFF
(many
communication
errors occurred)

Controller has received too many
faulty telegrams via the system
bus and has been disconnected
from the bus

l

Check bus termination

l

Check shield connection of the
cables

l

Check PE connection

l

Check bus load, reduce the baud
rate, if necessary

ce5

a

66

CAN time−out
(configurable in
C0126)

For remote parameterisation via
the system bus (C0370):
Slave does not respond.
Communication monitoring time
has been exceeded

l

Check wiring of the system bus

l

Check system bus configuration

For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly

The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
parameter sets

For operation with module on
FIF:
Internal error

Contact Lenze