Commissioning

Parameter setting with E82ZBC keypad
Vector control

7

l

138

EDK82EV222 DE/EN/FR 13.0

Comment

Switch−on sequence

15.

Enter the motor data

See motor nameplate

A

Rated motor speed (C0087)
Lenze setting: 1390 rpm

B

Rated motor current (C0088)
Lenze setting: Depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

C

Rated motor frequency (C0089)
Lenze setting: 50 Hz

D

Rated motor voltage (C0090)
Lenze setting: Depending on the controller

Enter the value for the motor circuit
configuration (star/delta) selected!

E

Motor cos

j (C0091)

Lenze setting: Depending on the controller

16.

Start the motor parameter identification (C0148)

Only when the motor is cold!

A

Ensure that the controller is inhibited

Terminal X3/28 = LOW

B

Set C0148 = 1

Press

v

C

Enable the controller

l

Terminal X3/28 = HIGH

l

The identification starts:
– Segment

c is off

– The motor consumes current and

makes a high−pitched" tone.

– The motor does not rotate!

D

If segment

c becomes active again after approx. 30 s,

inhibit controller again.

l

Terminal X3/28 = LOW

l

Identification is completed.

l

Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance (C0092)

l

Measured and stored:
– Motor stator resistance (C0084) = Total

resistance of motor cable and motor

17.

If necessary, select more parameters

Activate e.g. JOG frequencies (C0037, C0038,
C0039) or motor temperature monitoring
(C0119)

When all settings are complete:

18.

Select setpoint

E.g. via potentiometer at terminals 7, 8, 9

19.

Enable the controller

Terminal X3/28 = HIGH

20.

The drive is now running.

If the drive does not start, additionally press

u