Emc-compliant wiring, Emc−compliant wiring – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 118

Advertising
background image

Electrical installation

Wiring
EMC−compliant wiring

5

l

118

EDK82EV222 DE/EN/FR 13.0

EMC−compliant wiring

(Design of a CE−typical drive system)

)

Note!

ƒ

Control cables and mains cables must be separated from the motor cable to avoid
interference injections.

ƒ

Always use shielded control cables.

ƒ

Generally we recommend to shield the cable for the PTC or thermal contact and
route it separately from the motor cable.

ƒ

If you route the cores for the motor connection and the cores for the connection of
the PTC or thermal contact within one cable with a common shield:

To reduce interference injections on the PTC cable we recommend to additionally
install the PTC kit type E82ZPEx.

ƒ

Optimum HF shield connection of the motor cable is obtained by using the terminal

2for motor PE and motor shield.