Relay output connection, Electrical installation – Lenze E82EV 8200 vector 0.25kW-2.2kW User Manual

Page 127

Advertising
background image

Electrical installation

Relay output connection

5

l

127

EDK82EV222 DE/EN/FR 13.0

Relay output connection

8200vec013

Function

Relay position

(activated)

Message

(Lenze setting)

Technical data

X1.2/K11

Relay output
normally−closed contact

opened

TRIP

AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.16 A

X1.2/K12

Relay mid−position
contact

X1.2/K14

Relay output
normally−open contact

closed

TRIP

PES

HF shield termination by PE connection through shield clamp

)

Note!

ƒ

Switching of control signals:

Use shielded cables

HF−shield termination by PE connection

The minimum load for switching the signals through correctly is 12 V and 5 mA.
Both values have to be exceeded at the same time.

ƒ

Switching of mains potentials:

Unshielded cables are sufficient

ƒ

For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!

ƒ

The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.

ƒ

The message that is output can be changed in code C0008 or C0415/1.