PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Appendix

C

RS485 (DSI) Protocol

PowerFlex 4M drives support the RS485 (DSI) protocol to allow
efficient operation with Rockwell Automation peripherals. In addition,
some Modbus functions are supported to allow simple networking.
PowerFlex 4M drives can be multi-dropped on an RS485 network using
Modbus protocol in RTU mode.

For information regarding DeviceNet or other communication protocols,
refer to the appropriate user manual.

Network Wiring

Network wiring consists of a shielded 2-conductor cable that is
daisy-chained from node to node.

Figure C.1 Network Wiring Diagram

Controller

01 02 03 04 05

11 12 13 14 15

06

16

*

W/T3

V/T2

U/T1

DC+ DC-

Master

PowerFlex 4M

Node 1

4

5

PowerFlex 4M

Node 2

4

5

PowerFlex 4M

Node "n"

4

5

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

120 ohm resistor

120 ohm resistor

FRONT

PIN 8

PIN 1

NOTE: The shield should be grounded at ONLY ONE location.

TxRxD+

TxRxD-

RS485

(DSI)

AK-U0-RJ45-TB2P

RS485

(DSI)

TxRxD+

TxRxD-

*Terminal block for Frame A and B drives
is shown here.

01 02 03 04 05

11 12 13 14 15

06

16

Shield

Shield

Shield

*

W/T3

V/T2

U/T1

DC+ DC-