P107, Basic program group, Continued) – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 50

Advertising
background image

3-10

Programming and Parameters

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Basic Program Group

(continued)

P107 [Stop Mode]

Related Parameter(s):

P106

,

A418

,

A425

,

A427

,

C304

Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to stop input except when

P106

[Start Source] is set for

“3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by

P107

[Stop Mode].

Options

0 “Ramp, CF”

(1)

(Default) Ramp to Stop. “Stop” command clears active fault.

1 “Coast, CF”

(1)

Coast to Stop. “Stop” command clears active fault.

2 “DC Brake, CF”

(1)

DC Injection Braking Stop. “Stop” command clears active
fault.

3 “DCBrkAuto,CF”

(1)

DC Injection Braking Stop with Auto Shutoff.

Standard DC Injection Braking for value set in

A424

[DC

Brake Time].
OR

Drive shuts off if the drive detects that the motor is
stopped.

“Stop” command clears active fault.

4 “Ramp”

Ramp to Stop.

5 “Coast”

Coast to Stop.

6 “DC Brake”

DC Injection Braking Stop.

7 “DC BrakeAuto”

DC Injection Braking Stop with Auto Shutoff.

Standard DC Injection Braking for value set in

A424

[DC

Brake Time].
OR

Drive shuts off if current limit is exceeded.

(1)

Stop input also clears active fault.