Programming and Parameters

3-9

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Basic Program Group

(continued)

P106 [Start Source]

Related Parameter(s):

d012

,

P107

Stop drive before changing this parameter.

Sets the control scheme used to start the drive.
Refer to

Start and Speed Reference Control on page 1-19

for details about how other drive settings

can override the setting of this parameter.
Important: For all settings except option 3, the drive must receive a leading edge from the start input
for the drive to start after a stop input, loss of power or fault condition.

Options

0 “Keypad” (Default)

Integral keypad controls drive operation.

I/O Terminal 1 “Stop” = coast to stop.

When active, the Reverse key is also active unless
disabled by

A434

[Reverse Disable].

1 “3-Wire”

I/O Terminal 1 “Stop” = stop according to the value set in

P107

[Stop Mode].

2 “2-Wire”

I/O Terminal 1 “Stop” = coast to stop.

3 “2-W Lvl Sens”

Drive will restart after a “Stop” command when:

Stop is removed
and

Start is held active

4 “2-W Hi Speed”

Important: There is greater potential voltage on the output
terminals when using this option.

Outputs are kept in a ready-to-run state. The drive will
respond to a “Start” command within 10 ms.

I/O Terminal 1 “Stop” = coast to stop.

5 “Comm Port”

(1)

Remote communications. Refer to

Appendix C

for details.

I/O Terminal 1 “Stop” = coast to stop.

(1)

When using option 5 “Comm Port”, if the drive is using a network for control and the user’s program
is maintaining a “Start” or “Jog” command without sending a “Stop command”, the drive will start
automatically when power is cycled.

!

ATTENTION:

Hazard of injury exists due to unintended operation. When

P106 [Start Source] is set to option 3, and the Run input is maintained, the
Run inputs do not need to be toggled after a Stop input for the drive to run
again. A Stop function is provided only when the Stop input is active (open).