Installation/Wiring

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Table 1.D Minimum Recommended Branch Circuit Protective Devices

Voltage
Rating

Drive Rating
kW (HP)

Fuse Rating

(1)

Amps

140M

(2)

(3)

Catalog No.

Recommended
MCS Contactors
Catalog No.

Min. Enclosure
Volume

(4)

Inches

3

120V AC –
1-Phase

0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.1 (1.5)

10
15
30
40

140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
140M-F8E-C32

100-C09
100-C12
100-C23
100-C30

1655
1655
1655
1655

240V AC –
1-Phase

0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)

10
10
15
35
40

140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
140M-D8E-C25
140M-F8E-C32

100-C09
100-C09
100-C12
100-C23
100-C30

1655
1655
1655
1655
1655

240V AC –
3-Phase

0.2 (0.25)
0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10.0)

3
6
10
15
25
35
45
60

140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C16
140M-D8E-C20
140M-F8E-C25
140M-F8E-C32
140M-F8E-C45

100-C09
100-C09
100-C09
100-C12
100-C23
100-C23
100-C37
100-C60

1655
1655
1655
1655
1655
1655
3441
3441

480V AC –
3-Phase

0.4 (0.5)
0.75 (1.0)
1.5 (2.0)
2.2 (3.0)
3.7 (5.0)
5.5 (7.5)
7.5 (10.0)
11.0 (15.0)

3
6
10
10
15
25
30
50

140M-C2E-B25
140M-C2E-B40
140M-C2E-C10
140M-C2E-C10
140M-C2E-C16
140M-D8E-C20
140M-F8E-C25
140M-F8E-C32

100-C09
100-C09
100-C09
100-C09
100-C12
100-C23
100-C23
100-C30

1655
1655
1655
1655
1655
3441
3441
3441

(1)

Recommended Fuse Type: UL Class J, RK1, T or Type BS88; 600V (550V) or equivalent.

(2)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M

Motor Protection Circuit Breakers Application Ratings

.

(3)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240
Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner
ground, or high-resistance ground systems.

(4)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be
installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this
column. Application specific thermal considerations may require a larger enclosure.