Advanced program group, Advanced program group -19, A401 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 59: A402, A401 [accel time 2, A402 [decel time 2, Programming and parameters 3-19

Programming and Parameters
3-19
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group
A401 [Accel Time 2]
Related Parameter(s):
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
for details.
Values
Default
20.0 Secs
Min/Max:
0.0/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceler
ation
Deceler
ation
A402 [Decel Time 2]
Related Parameter(s):
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart
on
for details.
Values
Default
20.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceler
ation
Deceler
ation