T211, T212, T213 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 54

Advertising
background image

3-14

Programming and Parameters

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

t201 &
t202
Options
(Cont.)

13 “10V In Ctrl”

Selects 0-10V or ±10V control as the frequency reference.
Start source is not changed.

14 “20mA In Ctrl”

Selects 4-20mA control as the frequency reference. Start
source is not changed.

15 “Anlg Invert”

Inverts the scaling of the analog input levels set in

t211

[Anlg In 0-10V Lo] and

t212

[Anlg In 0-10V Hi] or

t213

[Anlg In4-20mA Lo] and

t214

[Anlg In4-20mA Hi].

16-27

Reserved

t211 [Anlg In 0-10V Lo]

Related Parameter(s):

d020

,

P104

,

P108

,

t201

,

t202

Sets the analog input level that corresponds to

P104

[Minimum Freq] if a 0-10V input is used by

P108

[Speed Reference].
Analog inversion can be accomplished by setting this value larger than

t212

[Anlg In 0-10V Hi] or by

setting

t201

-

t202

[Digital Inx Sel] to option 15 “Anlg Invert”.

Values

Default

0.0%

Min/Max:

0.0/ 100.0%

Display:

0.1%

0

P105 [Maximum Freq]

P104 [Minimum Freq]

t211 [Anlg In 0-10V Lo]

t212 [Anlg In 0-10V Hi]

0

Speed Ref

erence

t212 [Anlg In 0-10V Hi]

Related Parameter(s):

d020

,

P105

,

P108

,

t201

,

t202

Sets the analog input level that corresponds to

P105

[Maximum Freq] if a 0-10V input is used by

P108

[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than

t211

[Anlg In 0-10V Lo] or by

setting

t201

-

t202

[Digital Inx Sel] to option 15 “Anlg Invert”.

Values

Default

100.0%

Min/Max:

0.0/ 100.0%

Display:

0.1%

t213 [Anlg In4-20mA Lo]

Related Parameter(s):

d021

,

P104

,

P108

,

t201

,

t202

Sets the analog input level that corresponds to

P104

[Minimum Freq] if a 4-20mA input is used by

P108

[Speed Reference].

Analog inversion can be accomplished by setting this value larger than

t214

[Anlg In4-20mA Hi] or by

setting

t201

-

t202

[Digital Inx Sel] to option 15 “Anlg Invert”.

Values

Default

0.0%

Min/Max:

0.0/ 100.0%

Display:

0.1%

Advertising