Advanced Program Group
(continued)
A446 [PWM Frequency]
Sets the carrier frequency for the PWM output waveform. The chart below provides derating
guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.
Values
Default
4.0 kHz
Min/Max:
2.0/10.0 kHz
Display:
0.1 kHz
% Output Curent (A)
68
84
88
80
76
96
100
92
72
64
60
56
52
Carrier Frequency (kHz)
8
7
6
5
4
3
2
1
10
9
A448 [SW Current Trip]
Related Parameter(s):
Enables/disables a software instantaneous (within 100 ms) current trip.
Values
Default
0.0 (Disabled)
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps