Programming and Parameters

3-27

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Advanced Program Group

(continued)

A446 [PWM Frequency]

Sets the carrier frequency for the PWM output waveform. The chart below provides derating
guidelines based on the PWM frequency setting.
Important: Ignoring derating guidelines can cause reduced drive performance.

Values

Default

4.0 kHz

Min/Max:

2.0/10.0 kHz

Display:

0.1 kHz

% Output Curent (A)

68

84

88

80
76

96

100

92

72

64
60
56
52

Carrier Frequency (kHz)

8

7

6

5

4

3

2

1

10

9

A448 [SW Current Trip]

Related Parameter(s):

P103

Enables/disables a software instantaneous (within 100 ms) current trip.

Values

Default

0.0 (Disabled)

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps