Programming and Parameters

3-3

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Display Group

d001 [Output Freq]

Related Parameter(s):

d002

,

d010

,

P104

,

P105

,

P108

Output frequency present at T1, T2 & T3 (U, V & W).

Values

Default

Read Only

Min/Max:

0.0/

P105

[Maximum Freq]

Display:

0.1 Hz

d002 [Commanded Freq]

Related Parameter(s):

d001

,

d013

,

P104

,

P105

,

P108

Value of the active frequency command. Displays the commanded frequency even if the drive is not
running.
Important: The frequency command can come from a number of sources. Refer to

Start and Speed

Reference Control on page 1-19

for details.

Values

Default

Read Only

Min/Max:

0.0/

P105

[Maximum Freq]

Display:

0.1 Hz

d003 [Output Current]

The output current present at T1, T2 & T3 (U, V & W).

Values

Default

Read Only

Min/Max:

0.00/(Drive Rated Amps

×

2)

Display:

0.01 Amps

d004 [Output Voltage]

Related Parameter(s):

P101

,

A453

,

A457

Output voltage present at terminals T1, T2 & T3 (U, V & W).

Values

Default

Read Only

Min/Max:

0/Drive Rated Volts

Display:

0.1 VAC

d005 [DC Bus Voltage]

Present DC bus voltage level.

Values

Default

Read Only

Min/Max:

Based on Drive Rating

Display:

1 VDC