Installation/Wiring

1-15

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

I/O Wiring Examples

12

+10V DC

Drive supplied power for 0-10V external potentiometer.
Maximum output current is 15mA.

P108

13

0-10V In

(3)

Not Active

For external 0-10V input supply
(input impedance = 100k ohm) or potentiometer wiper.

P108

14

Analog Common

For 0-10V In or 4-20mA In. Electronically isolated with
analog inputs from digital I/O.

15

4-20mA In

(3)

Not Active

For external 4-20mA input supply
(input impedance = 250 ohm).

P108

16

RS485 (DSI) Shield

Terminal should be connected to safety ground - PE
when using the RS485 (DSI) communications port.

(3)

Only one analog frequency source may be connected at a time. If more than one reference is connected at the same
time, an undetermined frequency reference will result.

No.

Signal

Default

Description

Param.

Input

Connection Example

Potentiometer
1-10k Ohm Pot.
Recommended
(2 Watt minimum)

P108

[Speed Reference] = 2 “0-10V Input”

Analog Input
0 to +10V, 100k ohm
impedance
4-20 mA, 100 ohm
impedance

Voltage

P108

[Speed Reference] = 2 “0-10V

Input”

Current

P108

[Speed Reference] = 3

“4-20mA Input”

Analog Input, PTC
For Drive Fault

Wire the PTC and External Resistor (typically matched to the PTC Hot
Resistance) to I/O Terminals 12, 13, 14.
Wire R2/R3 Relay Output (SRC) to I/O Terminals 5 & 11.

t201

[Digital In1 Sel] = 3 “Aux Fault”

t221

[Relay Out Sel] = 10 “Above Anlg V”

t222

[Relay Out Level] = % Voltage Trip

12

13

14

13

14

+

Common

14

15

Common

+

11

12

13

14

R2

R3

05

V

Trip

=

×

100

R

PTC (hot)

R

PTC (hot)

+ R

e

R

e

R

PTC