Accel/decel selection, 20 installation/wiring – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 30

1-20
Installation/Wiring
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Accel/Decel Selection
The selection of Accel/Decel rates can be made through digital inputs,
RS485 (DSI) communications and/or parameters.
Jog Input
Enabled and Active:
t201 or t202 = 2
Yes
A405 [Jog Accel/Decel] used.
P109 [Accel Time 1]/P110 [Decel Time 1]
are used.
RS485 (DSI) Port
Controls Speed
Active when
A401 [Accel Time 2]/A402 [Decel Time 2]
is selected by RS485 (DSI) port.
Input is programmed
as “Accel 2 & Decel 2”
t201 or t202 = 1
A401 [Accel Time 2]/A402 [Decel Time 2]
is active when input is active.
Speed is controlled
by [Preset Freq x]
t201 or t202 = 4
P109 [Accel Time 1]/P110 [Decel Time 1];
A401 [Accel Time 2]/A402 [Decel Time 2]
determined by the active Preset Frequency.
See A410-A413 [Preset Freq 0-3]
on
.
No
No
Yes
Yes
Yes
No
No