Parameter configuration, Supported modbus function codes – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 103

Advertising
background image

RS485 (DSI) Protocol

C-3

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Parameter Configuration

The following PowerFlex 4M parameters are used to configure the drive
to operate on a network.

Supported Modbus Function Codes

The peripheral interface (DSI) used on PowerFlex 4M drives supports
some of the Modbus function codes.

Important: Modbus devices can be 0-based (registers are numbered

starting at 0) or 1-based (registers are numbered starting at
1). Depending on the Modbus Master used, the register
addresses listed on the following pages may need to be
offset by +1. For example, Logic Command may be register
address 8192 for some master devices (e.g. ProSoft
3150-MCM SLC Modbus scanner) and 8193 for others
(e.g. PanelViews).

Parameter

Details

Reference

P106

[Start Source]

Set to 5 “RS485 (DSI) Port” if Start is controlled from
the network.

Page 3-9

P108

[Speed Reference]

Set to 5 “RS485 (DSI) Port” if the Speed Reference is
controlled from the network.

Page 3-11

C302

[Comm Data Rate]

Sets the data rate for the RS485 (DSI) Port. All nodes
on the network must be set to the same data rate.

Page 3-17

C303

[Comm Node Addr]

Sets the node address for the drive on the network.
Each device on the network requires a unique node
address.

Page 3-17

C304

[Comm Loss Action] Selects the drive’s response to communication problems.

Page 3-17

C305

[Comm Loss Time]

Sets the time that the drive will remain in
communication loss before the drive implements A105
[Comm Loss Action].

Page 3-18

C306

[Comm Format]

Sets the transmission mode, data bits, parity and stop
bits for the RS485 (DSI) Port. All nodes on the network
must be set to the same setting.

Page 3-18

Modbus Function Code (Decimal)

Command

03

Read Holding Registers

06

Preset (Write) Single Register

16 (10 Hexadecimal)

Preset (Write) Multiple Registers

Advertising