Installation/Wiring

1-19

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

The drive speed command can be obtained from a number of different
sources. The source is normally determined by

P108

[Speed Reference].

However, when

t201

or

t202

Digital Inx Sel is set to option 2, 4, 5 or 6,

and the digital input is active,

t201

or

t202

will override the speed

reference commanded by

P108

[Speed Reference]. See the chart below

for the override priority.

Start and Speed Reference Control

Jog Input

Enabled and Active:

t201 or t202 = 2

Yes

Drive will Start and Run at Jog Speed.

Direction comes from

Terminal 03 Dir/Run REV

Local/Remote Input

Enabled and Active:

t201 or t202 = 5

Yes

Start, Speed and Direction commands

come from Integral Keypad.

Comm Select Input
Enabled and Active:

t201 or t202 = 6

Yes

Start, Speed and Direction commands

come from RS485 (DSI) port.

P108 [Speed Reference]

= 4 or 5

Yes

Run as specified by

P108 [Speed Reference].

Start and Direction commands come

from P106 [Start Source].

t201 / t202

Preset Inputs Active

Yes

Run as specified by

A411-A413 [Preset Freq 1-3].

Start and Direction commands come

from P106 [Start Source].

Run as specified by

P108 [Speed Reference].

Start and Direction commands

come from P106 [Start Source].

No

No

No

No

No