Programming and Parameters

3-21

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Advanced Program Group

(continued)

A410 [Preset Freq 0]

(1)

A411 [Preset Freq 1]
A412 [Preset Freq 2]
A413 [Preset Freq 3]

Related Parameter(s):

P108

,

P109

,

P110

,

t201

,

t202

,

A401

,

A402

Values

A410 Default
A411 Default
A412 Default
A413 Default

0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz

Min/Max:

0.0/400.0 Hz

Display:

0.1 Hz

Provides a fixed frequency command value when

t201

-

t202

[Digital Inx Sel] is set to 4 “Preset

Frequencies”.
An active preset input will override speed command as shown in the flowchart on

page 1-20

.

(1)

To activate

A410

[Preset Freq 0] set

P108

[Speed Reference] to option 4 “Preset Freq 0-3”.

Input State of Digital In 1

(I/O Terminal 05)

Input State of Digital In 2

(I/O Terminal 06)

Frequency Source

Accel / Decel Parameter Used

(2)

0

0

A410

[Preset Freq 0]

[Accel Time 1] / [Decel Time 1]

1

0

A411

[Preset Freq 1]

[Accel Time 1] / [Decel Time 1]

0

1

A412

[Preset Freq 2]

[Accel Time 2] / [Decel Time 2]

1

1

A413

[Preset Freq 3]

[Accel Time 2] / [Decel Time 2]

(2)

When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in
this table.

A418 [Skip Frequency]

Related Parameter(s):

A419

Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.

Values

Default

0 Hz

Min/Max:

0/400 Hz

Display:

1 Hz