P111, P110, Basic program group – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 52: Continued), P110 [decel time 1, P111 [motor ol ret, P112 [reset to defalts

3-12
Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Basic Program Group
(continued)
P110 [Decel Time 1]
Related Parameter(s):
,
,
-
Sets the rate of deceleration for all speed decreases.
Values
Default
10.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=
Speed
0
Time
P105 [Maximum Freq]
P109 or A401
[Accel Time x]
P110 or A402
[Decel Time x]
0
Acceler
ation
Deceler
ation
P111 [Motor OL Ret]
Related Parameter(s):
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.
Options
0 “Disabled” (Default)
1 “Enabled”
P112 [Reset To Defalts]
Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options
0 “Idle State” (Default)
1 “Reset Defaults”
•
After the reset function is complete, this parameter will set
itself back to “0”.
•
Causes an F48
fault.