Basic Program Group

(continued)

P110 [Decel Time 1]

Related Parameter(s):

P108

,

P109

,

t201

,

t202

,

A402

,

A410

-

A413

Sets the rate of deceleration for all speed decreases.

Values

Default

10.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Decel Time

Decel Rate

=

Speed

0

Time

P105 [Maximum Freq]

P109 or A401
[Accel Time x]

P110 or A402

[Decel Time x]

0

Acceler

ation

Deceler

ation

P111 [Motor OL Ret]

Related Parameter(s):

P103

Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.

Options

0 “Disabled” (Default)

1 “Enabled”

P112 [Reset To Defalts]

Stop drive before changing this parameter.

Resets all parameter values to factory defaults.

Options

0 “Idle State” (Default)

1 “Reset Defaults”

After the reset function is complete, this parameter will set
itself back to “0”.

Causes an F48

Params Defaulted

fault.