Troubleshooting

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Drive does not Start from Start or Run Inputs wired to the terminal block.

Drive does not respond to changes in speed command.

Cause(s)

Indication

Corrective Action

Drive is Faulted

Flashing red status light

Clear fault.

Press Stop

Cycle power

Set

A450

[Fault Clear] to option 1

“Clear Faults”.

Cycle digital input if

t201

-

t202

[Digital Inx Select] is set to option
7 “Clear Fault”.

Incorrect programming.

P106

[Start Source] is set to

option 0 “Keypad” or option 5
“RS485 (DSI) Port”.

t201

-

t202

[Digital Inx Select] is

set to option 5 “Local” and the
input is active.

None

Check parameter settings.

Incorrect input wiring.
See

1-15

for wiring examples.

2 wire control requires Run
Forward, Run Reverse or Jog
input.

3 wire control requires Start and
Stop inputs

Stop input is always required.

None

Wire inputs correctly and/or install
jumper.

Incorrect Sink/Source DIP switch
setting.

None

Set switch to match wiring scheme.

Cause(s)

Indication

Corrective Action

No value is coming from the
source of the command.

The drive “Run” indicator is lit
and output is 0 Hz.

Check

d012

[Control Source] for

correct source.

If the source is an analog input,
check wiring and use a meter to
check for presence of signal.

Check

d002

[Commanded Freq]

to verify correct command.

Incorrect reference source is
being selected via remote
device or digital inputs.

None

Check

d012

[Control Source] for

correct source.

Check

d014

[Dig In Status] to

see if inputs are selecting an
alternate source. Verify settings
for

t201

-

t202

[Digital Inx Select].

Check

P108

[Speed Reference]

for the source of the speed
reference. Reprogram as
necessary.

Review the Speed Reference
Control chart on

page 1-19

.