Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 14

Advertising
background image

1-4

Installation/Wiring

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Figure 1.2 Phase to Ground MOV Removal

Input Power Conditioning

The drive is suitable for direct connection to input power within the rated
voltage of the drive (see

Appendix A

). Listed in

Table 1.C

are certain

input power conditions which may cause component damage or
reduction in product life. If any of the conditions exist, as described in

Table 1.C

, install one of the devices listed under the heading Corrective

Action on the line side of the drive.

Important: Only one device per branch circuit is required. It should be

mounted closest to the branch and sized to handle the total
current of the branch circuit.

Table 1.C Input Power Conditions

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(1)

or Isolation Transformer

(1)

Refer to

Appendix B

for accessory ordering information.

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Line has frequent power interruptions

Line has intermittent noise spikes in excess of
6000V (lightning)

Phase to ground voltage exceeds 125% of normal
line to line voltage

Remove MOV jumper to ground.

or Install Isolation Transformer
with grounded secondary if
necessary.

Ungrounded distribution system

R/L1
S/L2
T/L3

1

2

3

4

Three-Phase

AC Input

Jumper