14 installation/wiring – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 24

Advertising
background image

1-14

Installation/Wiring

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Figure 1.5 Control Wiring Block Diagram

No.

Signal

Default

Description

Param.

R1

Relay N.O.

Fault

Normally open contact for output relay.

t221

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

t221

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch
setting.

01

Stop

(1)

Coast

The factory installed jumper or a normally closed input
must be present for the drive to start.

P106

(1)

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To
disable reverse operation, see A095 [Reverse Disable].

P106

,

P107

03

Direction/Run REV

Not Active

P106

,

P107

,

A434

04

Digital Common

For digital inputs. Electronically isolated with digital inputs
from analog I/O.

05

Digital Input 1

Preset Freq

Program with t201 [Digital In1 Sel].

t201

06

Digital Input 2

Preset Freq

Program with t202 [Digital In2 Sel].

t202

11

+24V DC

Drive supplied power for digital inputs.
Maximum output current is 100mA.

01

02

03

04

05

06

11

12

13

14

15

16

Stop

(1)

Start/Run FWD

(2)

Direction/Run REV

Digital Common

Digital Input 1

Digital Input 2

R1

R2

R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC

+10V DC

0-10V In

Analog Common

4-20mA In

RS485 Shield

+24V

+10V

SRC

SNK

Typical

SNK Wiring

Typical

SRC Wiring

R1 R2 R3

1

8

RS485

(DSI)

SNK

SRC

01

02

03

04

05

06

11

12

13

14

15

16

(1)

Potentiometer
must be
1-10k ohm
2 Watt Min.

30V DC 125V AC 240V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

(1)

Important: I/O Terminal 01 is always a coast to stop input except

when P106 [Start Source] is set to “3-Wire” control. In three wire
control, I/O Terminal 01 is controlled by P107 [Stop Mode]. All other
stop sources are controlled by P107 [Stop Mode].

Important: The drive is shipped with a jumper installed between I/O
Terminals 01 and 11. Remove this jumper when using I/O Terminal
01 as a stop or enable input.

(2)

Two wire control shown. For three wire control use a momentary

input

on I/O Terminal 02 to command a start. Use a

maintained input

for I/O Terminal 03 to change direction.

P106

[Start Source]

Stop

I/O Terminal 01

Stop

Keypad

Per P107

Coast

3-Wire

Per P107

Per P107

2-Wire

Per P107

Coast

RS485 Port

Per P107

Coast