Installation/Wiring

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Table 1.F Power Terminal Block Specifications

Motor Start/Stop Precautions

DC+

(2)

, DC-

(2)

DC Bus Connection

BR+

(1)

, BR-

(1)

Dynamic Brake Resistor Connection
Safety Ground - PE

(1)

For Frame C only [5.5 kW (7.5 HP) ratings and higher].

(2)

Not applicable to 120 V, 1-Phase drives.

Terminal

Description

Frame

Maximum Wire Size

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Minimum Wire Size

(1)

Torque

A

3.3 mm

2

(12 AWG)

0.8 mm

2

(18 AWG)

1.4-1.6 N-m (12-14 lb.-in.)

B

8.4 mm

2

(8 AWG)

0.8 mm

2

(18 AWG)

1.6-1.9 N-m (14-17 lb.-in.)

C

13.3 mm

2

(6 AWG)

3.3 mm

2

(12 AWG)

2.7-3.2 N-m (24-28 lb.-in.)

!

ATTENTION: A contactor or other device that routinely disconnects
and reapplies the AC line to the drive to start and stop the motor can
cause drive hardware damage. The drive is designed to use control input
signals that will start and stop the motor. If used, the input device must
not exceed one operation per minute or drive damage can occur.

!

ATTENTION: The drive start/stop control circuitry includes
solid-state components. If hazards due to accidental contact with
moving machinery or unintentional flow of liquid, gas or solids exist,
an additional hardwired stop circuit may be required to remove the AC
line to the drive. When the AC line is removed, there will be a loss of
any inherent regenerative braking effect that might be present - the
motor will coast to a stop. An auxiliary braking method may be
required.