3-18

Programming and Parameters

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Communications Group

(continued)

C305 [Comm Loss Time]

Related Parameter(s):

d015

,

C304

Sets the time that the drive will remain in communication loss before implementing the option selected
in

C304

[Comm Loss Action].

Values

Default

5.0 Secs

Min/Max:

0.1/ 60.0 Secs

Display:

0.1 Secs

C306 [Comm Format]

Selects the protocol (RTU only), data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1
stop bit only) used by the RS485 port on the drive.
Refer to

Appendix C

for details on using the drive communication features.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “RTU 8-N-1” (Default)

1 “RTU 8-E-1”

2 “RTU 8-O-1”

3 “RTU 8-N-2”

4 “RTU 8-E-2”

5 “RTU 8-O-2”

C307 [Comm Write Mode]

Determines whether parameter changes made over communication port are saved and stored in
Non-Volatile Storage (NVS) or RAM only. If they are stored in RAM, the values will be lost at
power-down.

Options

0 “Save” (Default)

1 “RAM Only”

!

ATTENTION:

Risk of equipment damage exists. If a controller is programmed to

write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly
exceed its life cycle and cause the drive to malfunction. Do not create a program that
frequently uses configurable outputs to write parameter data to NVS unless C307
[Comm Write Mode] is set to option 1.