A453, Advanced program group, Continued) – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 69: A453 [boost select

Advertising
background image

Programming and Parameters

3-29

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Advanced Program Group

(continued)

A453 [Boost Select]

Related Parameter(s):

d004

,

P101

,

P102

Sets the boost voltage (% of

P101

[Motor NP Volts]) and redefines the Volts per Hz curve.

(1)

(1)

Drive may add additional voltage unless option 5 is selected.

Options

1 “30.0, VT”

Variable Torque

2 “35.0, VT”

3 “40.0, VT”

4 “45.0, VT”

5 “0.0 no IR”

Constant Torque

6 “0.0”

7 “2.5, CT”

[Default for

3.7, 5.5, 7.5 & 11.0 kW

(5.0, 7.5, 10.0 & 15.0 HP) Drives]

8 “5.0, CT” (Default)

9 “7.5, CT”

10 “10.0, CT”

11 “12.5, CT”

12 “15.0, CT”

13 “17.5, CT”

14 “20.0, CT”

% P102 [Motor NP Hertz]

% P101 [Motor NP

V

olts]

100

50

1/2 [Motor NP Volts]

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5-14