A453, Advanced program group, Continued) – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 69: A453 [boost select
![background image](/manuals/576950/69/background.png)
Programming and Parameters
3-29
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group
(continued)
A453 [Boost Select]
Related Parameter(s):
,
Sets the boost voltage (% of
[Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options
1 “30.0, VT”
Variable Torque
2 “35.0, VT”
3 “40.0, VT”
4 “45.0, VT”
5 “0.0 no IR”
Constant Torque
6 “0.0”
7 “2.5, CT”
[Default for
3.7, 5.5, 7.5 & 11.0 kW
(5.0, 7.5, 10.0 & 15.0 HP) Drives]
8 “5.0, CT” (Default)
9 “7.5, CT”
10 “10.0, CT”
11 “12.5, CT”
12 “15.0, CT”
13 “17.5, CT”
14 “20.0, CT”
% P102 [Motor NP Hertz]
% P101 [Motor NP
V
olts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1
0
50
100
Settings