Installation/Wiring

1-3

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Storage

Store within an ambient temperature range of -40° to +85°C.

Store within a relative humidity range of 0% to 95%,
non-condensing.

Do not expose to a corrosive atmosphere.

Ungrounded Distribution Systems

Disconnecting MOVs

To prevent drive damage, the MOVs connected to ground shall be
disconnected if the drive is installed on an ungrounded distribution
system where the line-to-ground voltages on any phase could exceed
125% of the nominal line-to-line voltage. To disconnect these devices,
remove the jumper shown in the Figures

1.1

and

1.2

.

1. Turn the screw counterclockwise to loosen.

2. Pull the jumper completely out of the drive chassis.

3. Tighten the screw to keep it in place.

Figure 1.1 Jumper Location (Frame A shown)

AC Supply Source Considerations

!

ATTENTION: PowerFlex 4M drives contain protective MOVs that
are referenced to ground. These devices must be disconnected if the
drive is installed on an ungrounded or resistive grounded distribution
system.

Important:
Tighten screw after
jumper removal.