Mount the drive upright on a flat, vertical and level surface.

Install on 35 mm DIN Rail (for frames A and B).
or

Install with screws.

Table 1.A Screw Mounting Recommendations

Protect the cooling fan by avoiding dust or metallic particles.

Do not expose to a corrosive atmosphere.

Protect from moisture and direct sunlight.

Minimum Mounting Clearances

Refer to

Appendix B

for mounting dimensions.

Ambient Operating Temperatures

Drive enclosure is rated IP20, NEMA/UL Type Open.

Mounting Considerations

Minimum Panel Thickness Screw Size

Mounting Torque

1.9 mm (0.0747 in.)

M4 (#8-32)

1.56-1.96 N-m (14-17 lb.-in.)

Table 1.B Enclosure and Clearance Requirements

Horizontal Clearance between drives

Ambient Temperature

Minimum

Maximum

0 mm and greater

-10°C (14°F)

40°C (104°F)

25 mm and greater

-10°C (14°F)

50°C (122°F)

76.2 mm (3.0 in.)

76.2 mm (3.0 in.)

Closest object that
may obstruct air flow
through the drive
heat sink and chassis

76.2 mm (3.0 in.)

76.2 mm (3.0 in.)

Airflow

See Table 1.B