Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 84

Advertising
background image

A-4

Supplemental Drive Information

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Category

Specification

Environment

Altitude:

1000 m (3300 ft) max. without derating

Maximum Surrounding Air
Temperature without derating:

IP20:
IP20 zero stacking:

–10 to 50° C (14 to 122° F)
–10 to 40° C (14 to 104° F)

Cooling Method

Convection:

Fan:

120V, 1-Phase, 0.75 kW (1 HP) and below
240V, 1-Phase, 0.4 kW (0.5 HP) and below
240V, 3-Phase, 0.75 kW (1 HP) and below
480V, 3-Phase, 0.75 kW (1 HP) and below

All other drive ratings.

Storage Temperature:

–40 to 85 degrees C (–40 to 185 degrees F)

Atmosphere:

Important: Drive must not be installed in an
area where the ambient atmosphere contains
volatile or corrosive gas, vapors or dust. If the
drive is not going to be installed for a period of
time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.

Relative Humidity:

0 to 95% non-condensing

Shock (operating):

15G peak for 11ms duration (±1.0ms)

Vibration (operating):

1G peak, 5 to 2000 Hz

Control

Carrier Frequency

2-10 kHz. Drive rating based on 4 kHz.

Frequency Accuracy

Digital Input:
Analog Input:

Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency.

Speed Regulation - Open Loop
with Slip Compensation:

±2% of base speed across a 40:1 speed range.

Stop Modes:

Multiple programmable stop modes including -
Ramp, Coast, DC-Brake, Ramp-to-Hold and

S Curve.

Acceleration/Deceleration:

Two independently programmable acceleration
and deceleration times. Each time may be
programmed from 0 - 600 seconds in 0.1 second
increments.

Intermittent Overload:

150% Overload capability for up to 1 minute
200% Overload capability for up to 3 seconds

Electronic Motor Overload
Protection

Provides class 10 motor overload protection
according to NEC article 430 and motor
over-temperature protection according to NEC
article 430.126 (A) (2). UL 508C File 29572.

Electrical

Voltage Tolerance:

200-240V ±10%
380-480V ±10%
460-600V ±10%

Frequency Tolerance:

48-63 Hz

Input Phases:

Three-phase input provides full rating. Single-phase
operation provides 35% rated current.

Displacement Power Factor:

0.98 across entire speed range

Maximum Short Circuit Rating:

100,000 Amps Symmetrical

Actual Short Circuit Rating:

Determined by AIC Rating of installed fuse/circuit
breaker

Transistor Type:

Isolated Gate Bipolar (IGBT)