A425 [DC Brake Level]

Related Parameter(s):

P107

,

A418

Defines the maximum DC brake current, in amps, applied to the motor when

P107

[Stop Mode] is set

to either “Ramp” or “DC Brake”.

Values

Default

Drive Rated Amps

×

0.05

Min/Max:

0.0/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

DC Injection Braking Mode

V

olts/S

p

eed

Voltage

Time

Stop Command

Speed

[DC Brake Level]

[DC Brake Time]

V

olts/S

p

eed

Ramp-to-Stop Mode

Time

Stop Command

[DC Brake Level]

[DC Brake Time]

Voltage

Speed

!

ATTENTION:

If a hazard of injury due to movement of equipment or material exists,

an auxiliary mechanical braking device must be used.

!

ATTENTION:

This feature should not be used with synchronous or permanent

magnet motors. Motors may be demagnetized during braking.

A427 [DB Resistor Sel]

Related Parameter(s):

A428

Stop drive before changing this parameter.

Enables/disables external dynamic braking. This parameter applies only to Frame C drives.

The drive is able to provide full braking indefinitely. Braking power is limited by the external DB
resistor. When this parameter is set to 1 “Normal RA Res” and an appropriate RA resistor is used (see
selection

Table B.C

), the drive provides calculated resistor overload protection. However, the drive

cannot protect against a brake IGBT failure.

Values

Default

0

Min/Max:

0/3

Display:

1

Setting

Min/Max

0
1
2
3

“Disabled”
“Normal RA Res” (5% Duty Cycle) - Refer to

Table B.C on page B-2

“No Protection” (100% Duty Cycle)
“% Duty Cycle” Limited (1% – 99% of Duty Cycle) - see

A428

!

ATTENTION:

A risk of fire exists if external braking resistors are not protected. The

external resistor package must be self-protected from over temperature or the protective
circuit shown in

Figure B.3 on page B-7

, or equivalent, must be supplied.