A441, A440, A444 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual

Page 66: Advanced program group, Continued), A440 [process factor, A441 [bus reg mode, A442 [current limit, A444 [motor ol select, 26 programming and parameters

Advertising
background image

3-26

Programming and Parameters

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Advanced Program Group

(continued)

A440 [Process Factor]

Related Parameter(s):

d010

Scales the value displayed by

d010

[Process Display].

Values

Default

30.0

Min/Max:

0.1/999.9

Display:

0.1

Output

Freq

Process

Factor

Process

Display

=

x

A441 [Bus Reg Mode]

Controls the operation of the drive voltage regulation, which is normally operational at deceleration or
when the bus voltage rises.
Refer to the Attention statement on page

P-3

for important information on bus regulation.

Values

0 “Disabled”

1 “Enabled” (Default)

A442 [Current Limit]

Maximum output current allowed before current limiting occurs.

Values

Default

Drive Rated Amps

×

1.5

Min/Max:

0.1/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

A444 [Motor OL Select]

Related Parameter(s):

P102

,

P103

Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I

2

t

overload function.

Options

0 “No Derate” (Default)

1 “Min Derate”

2 “Max Derate”

Min Derate

0

80

100

60

40

20

% of P10

3 [Motor OL Curent]

No Derate

0

80

100

60

40

20

% of P102 [Motor NP Hertz]

% of P10

3 [Motor OL Curent]

% of P102 [Motor NP Hertz]

% of P10

3 [Motor OL Curent]

% of P102 [Motor NP Hertz]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25