Basic Program Group

P101 [Motor NP Volts]

Related Parameter(s):

d004

,

A453

Stop drive before changing this parameter.

Set to the motor nameplate rated voltage.

Values

Default

Based on Drive Rating

Min/Max:

20/Drive Rated Voltage

Display:

1 VAC

P102 [Motor NP Hertz]

Related Parameter(s):

A453

,

A444

Stop drive before changing this parameter.

Set to the motor nameplate rated frequency.

Values

Default

60 Hz

Min/Max:

10/400 Hz

Display:

1 Hz

P103 [Motor OL Current]

Related Parameter(s):

P111

,

t221

,

A441

,

A444

,

A448

,

A437

Set to the maximum allowable motor current.

The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60
seconds or 200% for 3 seconds.

Values

Default

Based on Drive Rating

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps

P104 [Minimum Freq]

Related Parameter(s):

d001

,

d002

,

d013

,

P105

,

t211

,

t213

,

A438

Sets the lowest frequency the drive will output continuously.

Values

Default

0.0 Hz

Min/Max:

0.0/400.0 Hz

Display:

0.1 Hz

P105 [Maximum Freq]

Related Parameter(s):

d001

,

d002

,

d013

,

P104

,

A404

,

t212

,

t214

,

A438

Stop drive before changing this parameter.

Sets the highest frequency the drive will output.

Values

Default

60 Hz

Min/Max:

0/400 Hz

Display:

1 Hz