Install the Switch Chapter 1

Required Tools and Equipment

Obtain these necessary tools and equipment:

Ratcheting torque screwdriver that exerts up to 1.69 N

m (15 in

lbs) of

pressure

#6 ring terminal lug for 5.3 mm

(10 AWG) wire, such as Thomas & Bett

part number 10RC6 or equivalent

Crimping tool, such as Thomas & Bett part number WT2000,

ERG-2001, or equivalent

5.3 mm

2

(10 AWG) copper ground wire, such as Belden part number 9912

or equivalent

Wire-stripping tool

For panel-mounting without a DIN rail, M5 or #10-24 or #10-32 bolts or

screws with 1.27 cm (0.5 in.) O.D. flat washers

For simplified cabling, the automatic medium-dependent interface crossover
(auto-MDIX) feature is enabled by default on the switch. With auto-MDIX
enabled, the switch detects the required cable type for copper Ethernet
connections and configures the interfaces accordingly. Therefore, you can use
either a crossover or a straight-through cable for connections to a switch 10/100
or 10/100/1000 Ethernet port, regardless of the type of device on the other end
of the connection.

For maximum noise immunity, shielded cables must be used on the uplink ports
(Gi1/1 and Gi1/2) on these switches:

1783-BMS06TGL
1783-BMS06TGA
1783-BMS10CGA
1783-BMS10CGL
1783-BMS10CGN
1783-BMS10CGP
1783-BMS20CGL
1783-BMS20CGN
1783-BMS20CGP
1783-BMS20CGPK

At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.