Mount the switch on a din rail – Rockwell Automation 1783-Mxxx Stratix 8000 and 8300 Ethernet Managed Switches User Manual User Manual

Page 24

Advertising
background image

24

Rockwell Automation Publication 1783-UM003I-EN-P - March 2014

Chapter 1 Install the Switch

4. Push the upper and lower module latches in to secure the module to the

switch.

5. If you are installing a second module, repeat steps

1

...

4

, but secure the

second module to the right side of the first module.

Mount the Switch
on a DIN Rail

Follow these steps to mount the switch on a DIN rail.

1. Insert a sharp tool, such as a screwdriver, in the space next to the tab, push

gently to release the catch, then turn the screwdriver to push the tab out.

IMPORTANT

You cannot install an expansion module to the right of the

1783-MX08F or 1783-MX08S fiber expansion module.

31781-M

WARNING: When using DIN rail mounting, additional grounding is also
accomplished through the DIN rail to chassis ground. Use zinc plated
yellow-chromate steel DIN rail to assist in proper grounding. The use of other
DIN rail materials (for example, aluminum or plastic)) that can corrode, oxidize,
or are poor conductors, can impede proper grounding. Secure DIN rail to
mounting surface approximately every 200 mm (7.8 in.) using end-anchors
appropriately and using a washer plate along the entire length of the DIN rail.

31776-M

Advertising