Rockwell Automation Publication 1783-UM003I-EN-P - March 2014

Chapter 1 Install the Switch

3. Insert the exposed wires for the external alarm device into the two

connections labeled A, as shown in the following figure.

4. Use a screwdriver to torque the power and relay connector captive screw

(above the installed wire leads) to 0.23 N•m (2.0 lb•in).

5. Repeat steps

1

4

to insert the input and output wires of an additional

external alarm device into the second power and relay connector.

The following figure shows the completed wiring for two power supplies
and two external alarm devices.

1

External device, relay wire A connection 1

2

External device, relay wire A connection 2

1

Power source A positive connection

5

Power source B positive connection

2

Power source A return connection

6

Power source B return connection

3

External device 1, relay wire major alarm connection 7

External device 2, relay wire minor alarm
connection

4

External device 1, relay wire major alarm connection 8

External device 2, relay wire minor alarm
connection

 -