103
Supported 1771 Modules Chapter 8
This data can be mapped to a numeric write tag.
Diagnostic Data
The 1771-NOC module returns 16 bits of diagnostic data.
This data can be mapped to a flag read tag.
3
Channel 4 data
4
Channel 5 data
5
Channel 6 data
6
Channel 6 data
7
Channel 7 data
1771-NOC Module Diagnostic Data
Bit
Description
0
Module good communication
1
reserved
2
reserved
3
reserved
4
reserved
5
reserved
6
reserved
7
reserved
8
Channel 1 data invalid
9
Channel 2 data invalid
10
Channel 3 data invalid
11
Channel 4 data invalid
12
Channel 5 data invalid
13
Channel 6 data invalid
14
Channel 7 data invalid
15
Channel 8 data invalid
1771-NOC Module I/O Data