Chapter

5

Configuring RSLogix 5000 Software to Access
Data on the 1757-ABRIO Module

Introduction

This chapter describes:

the operating modes of the 1757-ABRIO module.

how to access data on the module from a ControlLogix
controller.

Modes of Operation

There are four modes of operation for the module.

CONFIG

INACTIVE (Program)

ACTIVE (Run)

FORCED ACTIVE

The mode of the 1757-ABRIO module determines the RIO network
mode.

Modes related to RIO network operations:

INACTIVE (Program) mode, digital inputs continue to update
but digital outputs and block transfers do not.

ACTIVE (Run) mode, digital inputs and outputs update, and
block transfers update.

CONFIG Mode

The module is in CONFIG mode while AbRioCfg software downloads
a configuration. CONFIG mode is largely invisible to the user unless
the configuration being downloaded is large. After downloading, the
software returns the module to INACTIVE mode.