Ok status indicator - module health, Status display power-up messages, Power supply indicator – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 136: Ok status indicator – module health

Advertising
background image

134

Publication 1757-UM007D-EN-P - December 2008

Appendix A Troubleshooting

OK Status Indicator – Module Health

Status Display Power-up
Messages

The alphanumeric display shows the following messages at power-up.

If the indicator on the 1757-ABRIO module does not cycle through
these messages on powerup, refer to the Troubleshooting section of
publication

1757-UM007C

, the 1757-ABRIO User Manual.

Power Supply Indicator

Indicator

Status

Green

Indicates that module has passed all power-up diagnostics and is
functioning normally.

Red

Indicates that module startup diagnostics have failed or a major module
fault such as watchdog time-out or jabber inhibit has occurred.

IMPORTANT

If all three status indicators are solid red and the 4-character
display shows the #xx, (where xx is the error number) this is
where the fatal area occurs. Refer to publication

1757-UM007C

, the 1757-ABRIO User Manual for information on

clearing fatal errors. Be sure to make a note of the error code
numbers to give Tech Support, if you need to call for help.

B#nn

Stages in the start-up processes, nn is a hexadecimal number

Boot

Next stage in power-up sequence

57ABRIO Ver x.xx.xx

Module firmware version

POWER Indicator

Power Supply Status

Recommended Action

Off

Not operating

Turn power switch ON.

Check power wiring connections.

Check fuse.

On

Operating

None, normal operation.