Chapter 1 Introduction

RSLogix 5000 System Quick
Start

Use the following steps to quickly get the module running in an
RSLogix 5000 system. Detailed information about each step is
available in other sections of this manual or in the installation manual.
You can only have one scanner per RIO network. Remove any other
scanners on the RIO network before continuing.

1. Install the 1757-ABRIO module in the chassis and connect it to

the RIO network.

See the Process Remote I/O (RIO) Communication Interface
Module Installation Instructions, publication

1757-IN916

.

2. Flash the Controller with the latest firmware.

See

Using ControlFlash Software on page 14

.

3. Install the AbRioCfg software.

See

Installing AbRioCfg Software on page 19

.

4. Autoconfigure or manually configure the RIO racks. This step

locates all connected racks.

See

Autoconfigure the I/O Racks on page 19

and

Add Racks

Offline on page 33

.

5. Add and configure block transfer modules.

See

Adding Block Transfer Modules on page 23

.

6. Create tags to access analog data from the ControlLogix

controller.

See

Create a Tag on page 30

.

OR

Use scheduled updates to access digital data from the
ControlLogix controller.

See

Scheduled Digital I/O Connections in RSLogix 5000

Programs on page 60

.

7. Map I/O data to the tags and save the configuration file.

See

Mapping Data to Tags in AbRioCfg Software on page 31

.

8. Download the configuration to 1757-ABRIO module.

See

Download the Configuration on page 35

.