Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 64

Advertising
background image

62

Publication 1757-UM007D-EN-P - December 2008

Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module

6. Type a Name and a Description for the module, if desired.

7. Set the Slot number for the module in the ControlLogix chassis.

8. For the Comm Format, select Data - INT - With Status.

9. Select the following values for the Connection Parameters.

10. Verify that the Open Module Properties checkbox is checked

and click OK.

11. Set the module’s Requested Packet Interval (RPI).

This is how often the module's scheduled data is updated in the
controller. The value can range from 0.2 to 750 ms. The default
time is 5 ms.

12. Click OK.

13. Save the program and download it to the ControlLogix

controller.

Assembly
Instance

Size

Input

1

250

Output

2

248

Configuration

4

0

Status Input

5

10

Status Output

6

N/A