Chapter 5 Configuring RSLogix 5000 Software to Access Data on the 1757-ABRIO Module

2. Create Message Commands to Read and Write All RIO
Network Data

RSLogix 5000 Example Message Commands in Program Mode

This table shows the source (write) or destination (read) data type to
use with each 1757-ABRIO tag type and the size for each type.

Use the Browse
button (

) to

locate the
read/write tags
you want to
reference in your
message
commands. See

Create a Tag on
page 30

for more

information.

ControlLogix Data types

1757-ABRIO Tag

Source/destination Type

Storage Data Size

Numeric read

REAL

64

Numeric write

REAL

64

Flag read

DINT

16

Flag Write

DINT

16

Text read

SINT

64