Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 134

Advertising
background image

132

Publication 1757-UM007D-EN-P - December 2008

Appendix A Specifications

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3

10V/m with 1 kHz sine-wave 80%AM from 80 MHz to 2000 MHz

10V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on communication ports

Surge Transient
Immunity

IEC 61000-4-5:

±2 kV line-earth (CM) on communication ports

Conducted RF
Immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz to 80 MHz

Enclosure Type
Rating

None (open-style)

North American
temperature code

T4A

Certifications

Certification

Value

Certifications

(when product is
marked)

(1)

c-UL-usUL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E219376.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada.
See UL File E314476.

CEEuropean Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

(1)

See the Product Certification link at

http://ab.com

for Declarations of Conformity, Certificates, and other

certification details.

Environmental Specifications