Status Tag
The status tag contains a global status as well as individual status flags
for all possible partial racks. The status bits are set if the rack with the
corresponding rack number and starting I/O group is configured in
the 1757-ABRIO module and is not communicating, and are 0
otherwise. If any configured rack is not communicating, the global
status is set.
The following table shows the contents of the Status Tag.
Status Tag
Address
Description
Local:<slot>:S.Data[0]
Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.
Local:<slot>:S.Data[1]
Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.
Local:<slot>:S.Data[2].0
Not used
Local:<slot>:S.Data[2].1
Not used
Local:<slot>:S.Data[2].2
Not used
Local:<slot>:S.Data[2].3
Not used
Local:<slot>:S.Data[2].4
Rack 1, I/O group 0 error
Local:<slot>:S.Data[2].5
Rack 1, I/O group 2 error
Local:<slot>:S.Data[2].6
Rack 1, I/O group 4 error
Local:<slot>:S.Data[2].7
Rack 1, I/O group 6 error
Local:<slot>:S.Data[2].8
Rack 2, I/O group 0 error
Local:<slot>:S.Data[2].9
Rack 2, I/O group 2 error
Local:<slot>:S.Data[2].10
Rack 2, I/O group 4 error
Local:<slot>:S.Data[2].11
Rack 2, I/O group 6 error
Local:<slot>:S.Data[2].12
Rack 3, I/O group 0 error
Local:<slot>:S.Data[2].13
Rack 3, I/O group 2 error
Local:<slot>:S.Data[2].14
Rack 3, I/O group 4 error
Local:<slot>:S.Data[2].15
Rack 3, I/O group 6 error
Local:<slot>:S.Data[3].0
Rack 4, I/O group 0 error
Local:<slot>:S.Data[3].1
Rack 4, I/O group 2 error
Local:<slot>:S.Data[3].2
Rack 4, I/O group 4 error
Local:<slot>:S.Data[3].3
Rack 4, I/O group 6 error
Local:<slot>:S.Data[3].4
Rack 5, I/O group 0 error
Local:<slot>:S.Data[3].5
Rack 5, I/O group 2 error
Local:<slot>:S.Data[3].6
Rack 5, I/O group 4 error
Local:<slot>:S.Data[3].7