Tag Descriptions for Scheduled Data in RSLogix 5000 Software Appendix C

Status Tag

The status tag contains a global status as well as individual status flags
for all possible partial racks. The status bits are set if the rack with the
corresponding rack number and starting I/O group is configured in
the 1757-ABRIO module and is not communicating, and are 0
otherwise. If any configured rack is not communicating, the global
status is set.

The following table shows the contents of the Status Tag.

Status Tag

Address

Description

Local:<slot>:S.Data[0]

Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.

Local:<slot>:S.Data[1]

Rack global status, 0 if all configured racks are
communicating with no errors, FFFF hex otherwise.

Local:<slot>:S.Data[2].0

Not used

Local:<slot>:S.Data[2].1

Not used

Local:<slot>:S.Data[2].2

Not used

Local:<slot>:S.Data[2].3

Not used

Local:<slot>:S.Data[2].4

Rack 1, I/O group 0 error

Local:<slot>:S.Data[2].5

Rack 1, I/O group 2 error

Local:<slot>:S.Data[2].6

Rack 1, I/O group 4 error

Local:<slot>:S.Data[2].7

Rack 1, I/O group 6 error

Local:<slot>:S.Data[2].8

Rack 2, I/O group 0 error

Local:<slot>:S.Data[2].9

Rack 2, I/O group 2 error

Local:<slot>:S.Data[2].10

Rack 2, I/O group 4 error

Local:<slot>:S.Data[2].11

Rack 2, I/O group 6 error

Local:<slot>:S.Data[2].12

Rack 3, I/O group 0 error

Local:<slot>:S.Data[2].13

Rack 3, I/O group 2 error

Local:<slot>:S.Data[2].14

Rack 3, I/O group 4 error

Local:<slot>:S.Data[2].15

Rack 3, I/O group 6 error

Local:<slot>:S.Data[3].0

Rack 4, I/O group 0 error

Local:<slot>:S.Data[3].1

Rack 4, I/O group 2 error

Local:<slot>:S.Data[3].2

Rack 4, I/O group 4 error

Local:<slot>:S.Data[3].3

Rack 4, I/O group 6 error

Local:<slot>:S.Data[3].4

Rack 5, I/O group 0 error

Local:<slot>:S.Data[3].5

Rack 5, I/O group 2 error

Local:<slot>:S.Data[3].6

Rack 5, I/O group 4 error

Local:<slot>:S.Data[3].7

Rack 5, I/O group 6 error

Advertising