I/o data, Diagnostic data, I/o data diagnostic data – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 96

Advertising
background image

94

Publication 1757-UM007D-EN-P - December 2008

Chapter 8 Supported 1771 Modules

I/O Data

The 1771-IR module returns 6 words of floating point data to the host
controller.

This data is mapped to a numeric read tag.

Diagnostic Data

The 1771-IR module returns 16 bits of diagnostic data to the host
controller.

This data can be mapped to a flag read tag.

1771-IR Module I/O Data

Data Word

Description

0

Channel 1 data

1

Channel 2 data

2

Channel 3 data

3

Channel 4 data

4

Channel 5 data

5

Channel 6 data

1771-IR Module Diagnostic Data

Data Bit

Description

0

Module good communication

1

Channel 1 underrange

2

Channel 2 underrange

3

Channel 3 underrange

4

Channel 4 underrange

5

Channel 5 underrange

6

Channel 6 underrange

7

reserved

8

Channel 1 overrange

9

Channel 2 overrange

10

Channel 3 overrange

11

Channel 4 overrange

12

Channel 5 overrange

13

Channel 6 overrange

14

reserved

15

reserved