Appendix B Operational Comparison Between the 1757-ABRIO Module and a PLC-5 System

Rack Missing

Good communication bit for the rack is cleared

Good communication bits for block transfer modules in
the rack are cleared

Digital data does not update

Digital inputs hold their last state

Digital outputs go to the state set on the rack last state
switch in the rack

Block transfers to the rack do not update

Data from block transfer read modules goes to Not a
Number (NaN)

Block transfer write data goes to the state configured on
the I/O module

Tags with digital or block transfer data mapped to the
rack continue to update

Front panel displays the missing rack for 5 seconds

RIO network status indicator is red

Status bit for the rack is cleared

Block transfers to modules in the
rack error

Digital data does not update

Digital inputs hold their last state

Digital outputs go to the state set
on the rack last state switch

Block transfer read data holds its
last state

Block transfer write data goes to
the state configured on the I/O
module

Block transfer module missing or
not responding

Good communication bit for the block transfer module is
never set

Block transfer doesn't update, BT ignored request
diagnostic counter slowly increments

Error with module location is entered in the scanner log
each time the BT is retried

Tags to which the module is mapped update

Initial configuration block transfer
write to the module fails, block
transfer error bit is set

Invalid configuration data to block
transfer module

Can not happen, configuration program should validate
configuration

Initial block transfer write to the
module fails, block transfer error bit is
set for that block transfer

Block transfer read to configured
input module fails

Good communication flag for module is cleared

Input data is set to Not a Number

(1)

Block transfer read error bit is set

Input data holds last state

Block transfer write to configured
output module fails

Good communication flag for module is cleared

Output data is set to a value that depends on the
module configuration or jumpers

Block transfer write error bit is set

Output data is set to a value that
depends on the module
configuration or jumpers

Flag write tag to digital rack times
out

1757-ABRIO module sets outputs mapped to the tag to the
state set on the backplane switches (last state or 0)

N/A

Flag read tag times out

Inputs continue to update in the 1757-ABRIO module.

N/A

Numeric read tag times out

Data continues to update in the 1757-ABRIO module but
nothing is reading them.

N/A

Numeric write tag times out

1757-ABRIO module sets block transfer write data mapped
to the tag to the state set by the user in the module
configuration. Possible choices (last state, etc.) depend on
the module.

N/A

Analog output data out of
configured range

Data invalid bit for the channel is set

Output for the channel clamped to min/max value

See specific output module
documentation for appropriate
response.

Exception Conditions Comparison Between a PLC-5 System and a 1757-ABRIO Module

Exception Condition Message

From 1757-ABRIO Perspective

From the PLC-5 Perspective