Creating a generic module in abriocfg software – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual
Page 50
48
Publication 1757-UM007D-EN-P - December 2008
Chapter 3 Creating Generic Modules in AbRioCfg Software
The sum of the lengths in the data definitions must match the length
in the “flag” line.
Example 1771-OFE Configuration File
Creating a Generic Module
in AbRioCfg software
To add a generic module in AbRioCfg software, complete the
following steps.
1. Right-click the rack to which the module will be added and
select Add Module.
EXAMPLE
flag, 32
0,8
2H,8
4,16
configbtw, 13 ; length 13
4, 0x8000 ; binary data format
6, 0x0fff ; maximum raw value channel 1
8, 0x0fff ; maximum raw value channel 2
10, 0x0fff ; maximum raw value channel 3
12, 0x0fff ; maximum raw value channel 4
databtw, 12
numeric, 4
0, 4, 0, 0, 4095, 0, 1000
1, 4, 1, 0, 4095, 0, 1000
2, 4, 2, 0, 4095, 0, 1000
3, 4, 3, 0, 4095, 0, 1000