Addressing modes for 1771 – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 26

Advertising
background image

24

Publication 1757-UM007D-EN-P - December 2008

Chapter 2 Configure the 1757-ABRIO Module

4. Select the slot location for the module.

To do this, you should be familiar with Allen-Bradley addresses
and, in particular, with 1771 addressing modes (see below).
See

I/O Module Documentation on page 84

for a list of related

ControlLogix documentation.

5. Click OK.

Addressing Modes for 1771

The 1771 chassis have three addressing modes - 1/2-slot, 1-slot and
2-slot addressing. The addressing mode is set by switches in the
backplane of the chassis and is set on a per-chassis basis. The
addressing mode determines how physical block transfer modules
map into logical addresses (rack, I/O group and slot).

In the following tables, the addresses used for modules in a 16-slot
rack in each addressing mode. The rack switches are set for rack 1,
starting I/O group 0.

As illustrated in the 2-slot addressing table below, the controller
addresses two I/O module slots as one I/O group. For example, for a
chassis at rack 1, starting I/O group 0, a block transfer module in the
first slot would be at address rack 1, I/O group 0, slot 0. A module in
the next slot would be at rack 1, I/O group 0, slot 1.

As illustrated in the 1-slot addressing table below, the controller
addresses one I/O module slot as one I/O group. For example, for a
chassis at rack 1, starting I/O group 0, a block transfer module in the
first slot would be at address rack 1, I/O group 0, slot 0. A module in
the next slot would be at rack 1, I/O group 1, slot 0.

2-Slot Addressing

Slot in chassis

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Rack

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

I/O Group

0

0

1

1

2

2

3

3

4

4

5

5

6

6

7

7

Slot

0

1

0

1

0

1

0

1

0

1

0

1

0

1

0

1

1-Slot Addressing

Slot in chassis

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Rack

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

I/O Group

0

1

2

3

4

5

6

7

0

1

2

3

4

5

6

7

Slot

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Advertising