Monitoring the status of a block transfer – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 81

Advertising
background image

Publication 1757-UM007D-EN-P - December 2008

79

Monitoring the 1757-ABRIO Module Chapter 7

If you attempt to monitor a tag that has not been downloaded to the
1757-ABRIO module, AbRioCfg software displays a message that
indicates there is a configuration mismatch between the configuration
in AbRioCfg software and the configuration in the 1757-ABRIO
module.

Monitoring the Status of a
Block Transfer

To monitor the current status of a block transfer, complete the
following steps.

1. Expand the chassis where the block transfer module you want

to monitor is located.

2. Select the module you want to monitor.

3. Right-click the module to highlight and select Monitor BT from

the menu.

The block transfer monitor displays the raw data for the block transfer
and some diagnostic information. For input modules there is both a
block transfer read and a block transfer write. The write consists of
configuration data.

The raw data can be displayed as hexadecimal, signed, or unsigned
integer. The default for block transfer data is hexadecimal.

Refer to the following table for diagnostic information on block
transfer reads.

TIP

Use the same procedure to monitor digital and text data.

Block Transfer Read Diagnostics

Counter

Description

State

Active/Inactive

Type

Module type

BTR Len

Block transfer read length

Req Update Time

Requested update time in the module configuration, in ms

Avg Update Time

Average update time for this block transfer read, in ms. This
is the average of the previous 8 updates.

Min Update Time

Minimum update time for this block transfer read, in ms

Max Update Time

Maximum update time for this block transfer read, in ms

Update Count

Running count of updates for this block transfer read