Output scaling – Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 29

Advertising
background image

Publication 1757-UM007D-EN-P - December 2008

27

Configure the 1757-ABRIO Module Chapter 2

Output Scaling

For output modules, you supply the floating point values you want to
correspond to the minimum and maximum raw output values.

ATTENTION

The minimum scale value may not be larger than the maximum
scale value

EXAMPLE

If a channel has a range of 1

5 V dc and you set the minimum

scaling value to 12.3 and the maximum scaling value to 77.4,
when you set the output value to 12.3, the module produces a
raw output value of 1 V dc. When you set the output value to
77.4, the module produces a raw output of 5 V dc.

If you set the value outside the minimum and maximum scaling
values, the raw output is clamped at the minimum or maximum.