Rockwell Automation 1757-ABRIO Process Remote I/O (RIO) Communication Interface Module User Manual

Page 152

Advertising
background image

150

Publication 1757-UM007D-EN-P - December 2008

Appendix C Tag Descriptions for Scheduled Data in RSLogix 5000 Software

The offset for the input data for any rack and the I/O group can
be found from:

offset = 8 * (rack - 1) + I/O group + 2

where the rack number is in decimal

The offset for the output data for any rack and the I/O group
can be found from:

offset = 8 * (rack - 1) + I/O group

where the rack number is in decimal

Local:<slot>:I.Data[10]

Rack 2, I/O group 0 inputs

...

Local:<slot>:I.Data[17]

Rack 2, I/O group 7 inputs

...

Local:<slot>:I.Data[242]

Rack 37 octal, I/O group 0 inputs

...

Local:<slot>:I.Data[249]

Rack 37 octal, I/O group 7 inputs

Output Tags

Address

Description

Local:<slot>:O.Data[0]

Rack 1, I/O group 0 outputs

Local:<slot>:O.Data[1]

Rack 1, I/O group 1 outputs

...

Local:<slot>:O.Data[7]

Rack 1, I/O group 7 outputs

Local:<slot>:O.Data[8]

Rack 2, I/O group 0 outputs

...

Local:<slot>:O.Data[15]

Rack 2, I/O group 7 outputs

...

Local:<slot>:O.Data[240]

Rack 37 octal, I/O group 0 outputs

...

Local:<slot>:O.Data[247]

Rack 37 octal, I/O group 7 outputs

Input Tags

Address

Description